CX-1010INSTALLATION/WIRING GUIDESK1659 Rev A
Page 8 * Power for frequency input sensors may be supplied by J5, pin 1. Total current should not exceed 150 mA . TD / RD +TD/ RD –COMMONRS485SERIALC
Page 9 WIRINGThis section contains the input, output and serial communications wiring information for the CX–1010.Please read this section prior to wi
Page 10INPUTSNOTE: The installation of this motor control must conform to area and local electrical codes. Refer to page9 before you begin wiring.AC
Page 11Lead Frequency(J5 pins 1, 2, 4, 5, 6)Frequency Input 1The LEAD FREQUENCY Input acts as the lead signal when the CX–1010 is in the Follower mod
Page 12Lead Frequency continued...Figure 8 Lead FrequencySingle Channel Single-Ended Sensor (Unidirectional)*Total currant draw from the +12V_Aux (J5
Page 13*Total currant draw from the +12V_Aux (J5-Pin 1) should notexceed 150 Milliamps.Figure 10 Feedback FrequencyQuadrature Single-Ended Sensor (Bi
Page 14Feedback Frequency continued...Figure 11 Feedback FrequencySingle Channel Differential Sensor (Unidirectional)Figure 12 Feedback FrequencySi
Page 15F–Stop(J6 pins 1,3)Digital Input 0F-STOP is a momentary input. When it is opened, theCX–1010 commands a zero speed immediately andignores the
Page 16Run(J6 pins 3, 5)Digital Input 3When the RUN input (J6, pin 5) is momentarily shortedto common, the CX–1010 enters the RUN state. As amomentar
Page 17Keypad Lockout(J7 pins 8, 9)Digital Input 6When the KEYPAD LOCKOUT input is closed, theControl Parameters that you have selected to "lock
Page 18Block Select C(J7 pins 3,4)Digital Input 10Use BLOCK SELECT C in conjunction with BLOCKSELECT A and BLOCK SELECT B inputs to select oneof the e
Page 19Increment Batch Count(J7 pins 6, 8)Digital Input 12INCREMENT BATCH COUNT is a momentary input.When it is closed, the CX–1010 increases the inte
Page 20Remote Scroll Up(J7 pins 8, 9)Digital Input 14REMOTE SCROLL UP is a maintained input. When it isclosed, any Control Parameter that you enter i
Page 21OUTPUTSNOTE: The installation of this motor control must conform to area and local electrical codes. Refer to page9 before you begin wiring.S
Page 22Dev Alarm 1(J2 pin 5)Digital Output 3The DEV ALARM 1 output is activated (relay energized) when the Ramped Reference minus the Feedbackis great
Page 2312345678910J2EXTERNALDCPOWERSUPPLY(50V Max)R1R2R3+V_DOZero SpeedHi Speed AlarmLow Speed AlarmDev Alarm 1Dev Alarm 2Batch DoneControl Output Dir
Page 24SERIAL COMMUNICATIONSNOTE: The installation of this motor control must conform to area and local electrical codes. Refer to page9 before you
Page 25Figure 31 CX-1010 Serial Communications Connections1. Shield only at one end of the cable.2. If you need to terminate the communication line,
Page 26—NOTES—
Page 27ANALOG I/O CARD (OPTIONAL)This section contains the mounting and wiring information for the Analog I/O Card. Please read this sectionprior to
Page 1Installation / Wiring GuideConfigurationMountingWiringInputsOutputsSerial CommunicationsAnalog IO (Optional)MountingWiringDeviceNet (Optional)Lo
Page 28—NOTES—
Page 29MOUNTINGThis section contains the mounting information for the CX–1010 Analog I/O card. Please read this section asyou mount the Analog I/O ca
Page 301) If the CX-1010 unit has power connected to it, remove the power. If the CX-1010 has beenmounted in your system, disable it from the system.
Page 31Figure 32 Removing the CPU BoardPower BoardCPU Board
Page 3213) Reinsert the CPU Board into the CX-1010 unit by aligning the CPU board with the top andbottom card edge connectors and gently push the boar
Page 33 Figure 33 Mounting the Analog I/O Card on the CPU Board
Page 34—NOTES—
Page 35WIRINGThis section contains the input and output wiring information for the CX–1010 Analog I/O Card. Please readthis section prior to wiring t
Page 36J1123TD / RD +TD/ RD –COMRS485SERIAL COMM12J3CONTROLOUTPUTTO DRIVECO_SIGCO_COM12345678910J2+V_DODO_0DO_1DO_2DO_3DO_4DO_5DO_6DO_7COMDIGITAL OUTP
Page 37INPUTSNOTE: Refer to pages 9 and 35 before you begin wiring.Figure 36 Analog Input 2: VoltageInputFigure 35 Analog Input 1: Voltage Input56
Page 2
Page 38Figure 37 Analog Input 1: CurrentInput234JA 0-20 mA InputCommon243 OhmAnalog Input 1:Current Input Wiring(JA, Pins 2,3,4)The Analog Input 1
Page 39Figure 39 Analog Input 1:Potentiometer Input12348JA +12V _Aux*Common+–Figure 40 Analog Input 2:Potentiometer Input15678JA +12V _Aux*Common+
Page 40OUTPUTSNOTE: Refer to pages 9 and 35 before you begin wiring.Figure 41 Analog Output: VoltageOutput91011JA ± 12V OutCommonAnalog Output:Vol
Page 41DEVICENET CARD (OPTIONAL)For the installation, wiring and operation of the optional DeviceNet card, refer to the CX-Series DeviceNetCard Techni
Page 42—NOTES—
Page 43LOGIC CONTROLThis section addresses the six digital inputs that control the CX-1010's operating state.The six digital inputs ( listed in b
Page 44Logic InputsF–Stop (Fast Stop) has priority over the other operating states. F-Stop forces the CO signal to “0” volts andmonitors the feedback
Page 45R–Stop (Ramp Stop) has the second highest operating priority. Use R-Stop to stop the drive with adeceleration ramp. The velocity command is r
Page 46H–Stop (Stop and Hold) has the third highest operating priority. Use H-Stop to stop the drive with adeceleration ramp. The velocity command i
Page 47Run has the fourth highest operating priority. Run is the primary operating state. Setpoint Mode (CP-102)determines the mode of operation for
Page 3CONFIGURATIONThis section will show you how to re-configure the CX-1010 for electrical compatibility. Complete thisprocedure prior to installat
Page 48Jog Forward has the fifth highest operating priority. Use Jog Fwd to “Jog” the drive Forward at the rateindicated in Jog SP (CP-215). The ac
Page 49Jog Reverse has sixth (the least) operating priority. Use Jog Revs to “Jog” the drive Forward at the rateindicated in Jog SP (CP-215). The a
Page 50—NOTES—
Page 51—NOTES—
Page 52CONTREX, INC.8900 Zachary Lane NorthMaple Grove, MN 55369 USAPhone (763) 424-7800 Fax (763) 424-8734
Page 4WARNINGYou will damage the CX-1010 if youapply 230 VAC to the AC Power inputwhile the AC Power Input Voltage switchis in the 115 V position.CONT
Page 5The AC Power Input Voltage switch is located on the rear of the CX-1010. The default configuration for theAC Power Input Voltage switch is 115
Page 63.6"(9.1 cm)7.2"(18.3 cm)7.7"(19.6 cm)*6.3"(16.3 cm)4.0"(10.2 cm)DOOR PANEL(3.65" .03" 9.27± .07cmCUTOUT(CU
Page 7MOUNTINGThis section contains instructions for mounting the CX–1010 in the door panel of an industrial electricalenclosure. The CX–1010 is pack