Jog Forward has the fifth highest operating priority. Use Jog Fwd to “Jog” the drive Forward at the rate
indicated in Jog SP (CP-215). The acceleration and deceleration ramps are dictated by Acl Tm Jog (CP-216),
Dcl Tm Jog (CP-218) and Jog SP (CP-215). After the Jog FWD input is deactivated and the ramped
reference has reached “0”, the CX-1010 automatically reverts to the R-Stop operating state.
To activate Jog Forward:
Activate Low (closed to common), Level Sensitive, Not-Latched
Use momentary contact - does not need to be maintained to remain active
RUN
JOG FWD
COMMON
F-STOP
R-STOP
H-STOP
COMMON
JOG FWD
RUN
Close Momentarily
5
6
8
1
2
4
3
J6
R-STOP
H-STOP
F-STOP
Figure 47 Jog Forward Input