MP-83 LIMIT STATUS
Limit Status (MP-83) displays the status of the Minimum Limit (CP-08) and the Maximim Limit
(CP-09) functions. A "1" in the display digit location for the respective function indicates that
function is limiting.
Not Used
Min Limit
Max Limit
Not Used
Code
CP-84 ANALOG INPUT ALLOCATION
CP-84 allocates the analog input to the desired function. Allocation is accomplished by entering
one of the following codes into CP-84:
0 = Not Used
1 = Lead Frequency Replacement
2 = Feedback Frequency Replacement
3 = Offset Function
4 = Setpoint 1 Replacement
5 = Setpoint 2 Replacement
6 = Setpoint 3 Replacement
7 = Setpoint 4 Replacement
CP-85 ANALOG INPUT ZERO
CP-85 is used to zero adjust the analog A/D input during calibration. The value displayed in
CP-85 is the percent (XXX.X%) of full range A/D voltage input.
CP-86 ANALOG INPUT SPAN
CP-86 is used to span adjust the analog A/D input during calibration. The value displayed in
CP-86 is the percent (XXX.X%) of full range A/D voltage input.