Contrex MLP-Trim Manuel d'utilisateur Page 101

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 216
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 100
3 - 61
Logic Outputs
Drive Enable activates the motor drive based on the Ramped Reference (MP-46) and
the feedback. The Ramped Reference (MP-46) is the calculated setpoint that is output
from the Acceleration/Deceleration routine.
Dig_Out1 or Dig_Out2 can be used as the Drive Enable output depending on the
setting of CP-10 and CP-11, respectively.
Drive Enable Logic (CP-74) determines which conditions of the Ramped Reference
(MP-46) and feedback will control the Drive Enable output. The factory defaults for
Drive Enable Logic (CP-74) are found in Table 3-49. To modify these default
parameter, refer to Table 3-50. If you are uncertain how to enter a Control Parameters,
review the
Operations: Keypad
section.
Table 3-49 Default Drive Enable Logic Control Parameter
CP Parameter Name Parameter Value
CP-10 Alarm 1 Format 15
CP-11 Alarm 2 Format 15
CP-74 Drive Enable Logic 0
Vue de la page 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 215 216

Commentaires sur ces manuels

Pas de commentaire